All Categories

Diesel Generator with Cummins Engine

You are here : Home > Product > Generator Set (Brand) > Diesel Generator with Cummins Engine

3
730-1200kW 10500V Open Dongkang Cummins Engine Diesel Generator in Quickly Start

730-1200kW 10500V Open Dongkang Cummins Engine Diesel Generator in Quickly Start


PT fuel injection system

Start quickly and reliably

High-performance shock absorption

Low fuel consumption
 

Inquiry
  • Standard
  • Performance
STANDARD
ISO 8528: AC generator set driven by reciprocating internal combustion engine
IEC 60034-1: Basic technical requirements for rotating electrical machines
YD/T 502: communication diesel generator set
GB/T 20136-2006: General test method for internal combustion engine power station
ADVANTAGE
PT fuel injection system constitutes EFC electronic governor, realizes remote operation control, and can be put into full load at one time according to rated power.
Start quickly and reliably at low temperatures, reduce exhaust gas emissions, and make the emissions meet the national standards.
Adopt advanced technology to optimize the combustion process, reduce fuel consumption and higher reliability.
High-performance shock absorption system and rigid base, low vibration.
Low fuel consumption, low failure rate, lower cost, high economy and safety.
Standardized design, comprehensive and intelligent products, strong versatility of parts and components, convenient installation and easy maintenance.
PERFORMANCE

Parameter

Unit

Performance

Frequency drop

%

≤3

Steady-state frequency band

%

≤0.5

Relative frequency setting drop range

%

≥3.5

Relative frequency setting rising range

%

≥2.5

Transient frequency deviation

100% sudden reduction power

%

≤+10

Sudden power

≤-7

Frequency recovery time

s

≤3

Relative frequency tolerance band

%

2

Steady-state voltage deviation

%

≤±1

Voltage unbalance

%

1

Transient voltage deviation

100% sudden reduction power

%

≤+20

Sudden power

≤-15

Voltage recovery time

s

≤4

Voltage modulation

%

0.3

Relative voltage setting range

%

≤±5

Voltage setting rate of change

%/s

0.2~1

Telephone harmonic factor

THF

%

<2

Phone influencing factors

TIF

/

<50

DRAWING

图片1 副本

OPERATING ENVIRONMENT

The main power (PRP) is the maximum power that the unit can continuously operate with variable load under standard environment (atmospheric pressure, relative humidity, ambient temperature) conditions, and allow 10% overload operation for 1 hour every 12 hours.

Altitude: ≤1000m (when >1000m, power correction is required)
Ambient temperature: 40°C (when >40°C, power correction is required)
Relative humidity: ≤60%
When the on-site operating conditions of the diesel generating set doesn’t meet the above conditions, the output power of the generator set must be corrected, and finally corrected coefficient, please consult us.

Genset ModelGenset Prime Power(kW)Genset Standby Power(kW)Power FactorRated VoltageFrequencyDimension (L×W×H) (mm)Weight(kg)Engine ModelNumber of CylindersBore×Stroke(mm)Displacement(L)Fuel Consumption(g/kW)SpeedCooling SystemStarting Method
Open Style(10500V)
Chongkang Cummins Generator
ATYOH-C730C730 800 0.8400V50HZ5160L×1770W×2340H10500 KTA38-G2A12159*15938.000 <2101500Water CoolingElectrical Starting
ATYOH-C800C800 880 0.8400V50HZ 5160L×1770W×2400H10500    KTA38-G512159*15938.000 <2101500Water CoolingElectrical Starting
ATYOH-C1000C1000 1100 0.8400V50HZ5760L×2010W×2460H12100 KTA50-G316159*15950.000 <2151500Water CoolingElectrical Starting
ATYOH-C1000CG1000 1100 0.8400V50HZ5760L×2200W×2366H10800 QSK38-G512159*15937.700 <2101500Water CoolingElectrical Starting
ATYOH-C1100C1100 1200 0.8400V50HZ6250L×2010W×2440H13200 KTA50-G816159*15950.300 <2201500Water CoolingElectrical Starting
ATYOH-C1200C1200 1320 0.8400V50HZ 6150L×2010W×2570H13300 KTA50-GS816159*15950.000 <2201500Water CoolingElectrical Starting
INQUIRY