200-550kW 400V Super Soundless Slient Chongkang Cummins Engine Diesel Generator
Lower emissions, low noise
Labyrinth air duct structure
Using high-quality steel
Compact structure, and excellent craftsmanship
- Standard
- Performance
STANDARD
- ISO 8528: AC generator set driven by reciprocating internal combustion engine
- IEC 60034-1: Basic technical requirements for rotating electrical machines
- YD/T 502: communication diesel generator set
- GB/T 20136-2006: General test method for internal combustion engine power station
ADVANTAGE
- Integrated building block structure design, small size, compact structure, and excellent craftsmanship.
- Efficient fuel supply system and air intake system, fuel atomization and mixing with air more fully, more complete combustion, lower emissions.
- Adopting a fully enclosed noise reduction design and an integrated impedance silencing system, which can reduce the noise of the unit by 15~35dB(A), and the overall noise of the unit is low.
- Adopt labyrinth air duct structure and dustproof design to balance the different requirements of ventilation and waterproof and dustproof. At the same time, it has been verified by repeated rain test and dustproof test. The standard protection level is IP23, and the highest protection level is IP43.
- Using high-quality steel and surface spraying treatment, it has strong anti-corrosion and anti-rust properties.
PERFORMANCE
Parameter | Unit | Performance | ||
Frequency drop | % | ≤3 | ||
Steady-state frequency band | % | ≤0.5 | ||
Relative frequency setting drop range | % | ≥3.5 | ||
Relative frequency setting rising range | % | ≥2.5 | ||
Transient frequency deviation | 100% sudden reduction power | % | ≤+10 | |
Sudden power | ≤-7 | |||
Frequency recovery time | s | ≤3 | ||
Relative frequency tolerance band | % | 2 | ||
Steady-state voltage deviation | % | ≤±1 | ||
Voltage unbalance | % | 1 | ||
Transient voltage deviation | 100% sudden reduction power | % | ≤+20 | |
Sudden power | ≤-15 | |||
Voltage recovery time | s | ≤4 | ||
Voltage modulation | % | 0.3 | ||
Relative voltage setting range | % | ≤±5 | ||
Voltage setting rate of change | %/s | 0.2~1 | ||
Telephone harmonic factor | THF | % | <2 | |
Phone influencing factors | TIF | / | <50 |
DRAWING
OPERATING ENVIRONMENT
The main power (PRP) is the maximum power that the unit can continuously operate with variable load under standard environment (atmospheric pressure, relative humidity, ambient temperature) conditions, and allow 10% overload operation for 1 hour every 12 hours.
- Altitude: ≤1000m (when >1000m, power correction is required)
- Ambient temperature: 40°C (when >40°C, power correction is required)
- Relative humidity: ≤60%
- When the on-site operating conditions of the diesel generating set doesn’t meet the above conditions, the output power of the generator set must be corrected, and finally corrected coefficient, please consult us.
Genset Model | Genset Prime Power(kW) | Genset Standby Power(kW) | Power Factor | Rated Voltage | Frequency | Dimension (L×W×H) (mm) | Weight(kg) | Engine Model | Number of Cylinders | Bore×Stroke(mm) | Displacement(L) | Fuel Consumption(g/kW) | Speed | Cooling System | Starting Method |
Silent Style(400V) | |||||||||||||||
Chongkang | |||||||||||||||
ATYS-C200C | 200 | 220 | 0.8 | 400V | 50HZ | 4060L×1520W×2193H | 3800 | MTA11-G2 | 6 | 125*147 | 10.800 | <220 | 1500 | Water Cooling | Electrical Starting |
ATYS-C200CF | 200 | 220 | 0.8 | 400V | 50HZ | 4200L×1370W×2283H | 3977 | NT855-GA | 6 | 140*152 | 14.000 | <220 | 1500 | Water Cooling | Electrical Starting |
ATYS-C220C | 220 | 242 | 0.8 | 400V | 50HZ | 4200L×1370W×2283H | 4000 | NTA855-G1A | 6 | 140*152 | 14.000 | <220 | 1500 | Water Cooling | Electrical Starting |
ATYS-C250C | 250 | 275 | 0.8 | 400V | 50HZ | 4060L×1520W×2193H | 3835 | MTAA11-G3 | 6 | 125*147 | 10.800 | <180 | 1500 | Water Cooling | Electrical Starting |
ATYS-C280C | 280 | 300 | 0.8 | 400V | 50HZ | 4200L×1370W×2283H | 4074 | NTA855-G2A | 6 | 140*152 | 14.000 | <210 | 1500 | Water Cooling | Electrical Starting |
ATYS-C300C | 300 | 330 | 0.8 | 400V | 50HZ | 4600L×1470W×2322H | 4248 | NTAA855-G7 | 6 | 140*152 | 14.000 | <220 | 1500 | Water Cooling | Electrical Starting |
ATYS-C320C | 320 | 350 | 0.8 | 400V | 50HZ | 4600L×1470W×2322H | 4268 | NTAA855-G7A | 6 | 140*152 | 14.000 | <220 | 1500 | Water Cooling | Electrical Starting |
ATYS-C320CF | 320 | 350 | 0.8 | 400V | 50HZ | 4600L×1570W×2372H | 4500 | QSNT-G3 | 6 | 140*152 | 14.000 | <220 | 1500 | Water Cooling | Electrical Starting |
ATYS-C360C | 360 | 400 | 0.8 | 400V | 50HZ | 4600L×1720W×2502H | 5385 | QSNT-G4X | 6 | 140*152 | 14.000 | <220 | 1500 | Water Cooling | Electrical Starting |
ATYS-C360CF | 360 | 400 | 0.8 | 400V | 50HZ | 4600L×1720W×2502H | 5385 | KTA19-G3 | 6 | 159*159 | 19.000 | <210 | 1500 | Water Cooling | Electrical Starting |
ATYS-C400C | 400 | 440 | 0.8 | 400V | 50HZ | 4600L×1720W×2502H | 5385 | KTA19-G3A | 6 | 159*159 | 19.000 | <210 | 1500 | Water Cooling | Electrical Starting |
ATYS-C440C | 440 | 480 | 0.8 | 400V | 50HZ | 4950L×1920W×2560H | 6035 | KTAA19-G5 | 6 | 159*159 | 19.000 | <210 | 1500 | Water Cooling | Electrical Starting |
ATYS-C460C | 460 | 506 | 0.8 | 400V | 50HZ | 4950L×1920W×2560H | 6035 | KTAA19-G6 | 6 | 159*159 | 19.000 | <220 | 1500 | Water Cooling | Electrical Starting |
ATYS-C500C | 500 | 550 | 0.8 | 400V | 50HZ | 4950L×1920W×2560H | 6035 | KTAA19-G6A | 6 | 159*159 | 19.000 | <210 | 1500 | Water Cooling | Electrical Starting |
ATYS-C550C | 550 | 570 | 0.8 | 400V | 50HZ | 5300L×2020W×2700H | 6500 | QSK19-G4 | 6 | 159*159 | 19.000 | <220 | 1500 | Water Cooling | Electrical Starting |